Distribution Cabinet

JP Series Integrated Distribution Box

An outdoor distribution box combining metering, outgoing circuits and reactive power compensation. The JP series serves the low-voltage side of pole-mounted transformers, with vertical or horizontal stainless-steel enclosures and configurable circuit protection.

Technical overview

Technical Parameters

Ratings are configuration options and cannot be combined independently. The selected model, electrical duty and installation conditions are confirmed together before ordering.

JP Integrated Distribution Box technical parameters
Transformer capacity30–400 kVA
Rated operating voltageAC 400 V
Auxiliary circuit voltageAC 220 V / AC 380 V
Rated frequency50 Hz
Rated currentUp to 630 A
Rated residual operating current30–300 mA, adjustable
Enclosure protectionIP54
Enclosure constructionVertical or horizontal; 2 mm stainless steel or stainless-steel double-layer composite panel
Ambient temperature−25°C to +40°C
AltitudeUp to 2,500 m
Relative humidityDaily and monthly average: no more than 90%

Construction & configuration

Product Features

  • Combines electricity metering, outgoing distribution and reactive power compensation in one outdoor enclosure.
  • Provides short-circuit, overload, overvoltage and residual-current protection according to the circuit configuration.
  • Front and rear doors provide access for operation and maintenance; the enclosed metering compartment includes provision for lead sealing.
  • Stainless-steel construction, galvanized internal mounting members and door seals support outdoor service.
  • Cable entries and ventilation arrangements are designed to limit rain and foreign-object ingress while allowing heat dissipation.

Where it is used

Typical Applications

Selection depends on the system voltage, load, circuit duty and installation conditions.

  • Low-voltage distribution for outdoor pole-mounted transformers
  • Urban and rural electricity-network upgrades
  • Integrated metering, compensation and outgoing feeder installations
Project enquiries

Specify JP Integrated Distribution Box for your project.

Send the model, quantity, electrical requirements and project drawings for a configuration review and quotation.