| Gas hazardous areas |
Zones 1 and 2; gas groups IIA, IIB and IIC, subject to the supplied configuration and certificate |
| Dust hazardous areas |
Zones 21 and 22; dust groups IIIA, IIIB and IIIC listed in the catalogue |
| Branch circuits |
4, 6, 8, 10 or 12; main-switch versions depend on the selected model |
| Main circuit current options |
63 A; 80–100 A; 125–250 A |
| Branch current options |
1–16 A; 20–25 A; 32–63 A; 80–125 A |
| Enclosure materials |
Die-cast aluminium alloy, or welded steel / stainless steel |
| Construction options |
Flameproof; or flameproof main chamber with increased-safety terminal chamber |
| Circuit protection |
Overload and short circuit; residual-current protection optional |
| Wiring arrangement |
Steel conduit or cable |
| Catalogue gas marking example |
Ex db IIC T4 Gb |
| Catalogue dust marking example |
Ex tb IIIC T130°C Db |
Select the exact enclosure, circuit arrangement and temperature class against the hazardous-area classification and the supplied equipment certificate. The catalogue includes different T4 and T6 examples; they are separate configurations.